FIRE SAFETY SURVEY REPORT - 2000 LIFE SAFETY CODE
Intermediate Care Facilities for the Mentally Retarded
APARTMENT HOUSE
K2
PART I — 32 or 33 — Residential Board & Care Occupancies — Requirements
PART II — 7.7 (101A, 2001) — Fire Safety Evaluation System for Board & Care (Optional)
Identifying information as shown in applicable records. Enter changes, if any, alongside each item, giving date of change.
2. NAME OF FACILITY
2. (A) MULTIPLE CONSTRUCTION (BLDGS)
2. (B) ADDRESS OF FACILITY (STREET, CITY, STATE, ZIP CODE) A.
A. BUILDING ________________
B. WING
B.
________________
4. DATE OF SURVEY
DATE OF PLAN APPROVAL
SURVEY UNDER:
9.
K4
E-Score
≤ 1.5
s None (No sprinkler system)
K0180
K3
E-SCORE
s Partially Sprinkleredsprinklered)
(Not all required areas are
C.
________________
C. FLOOR
s Fully Sprinklered sprinklered)
(All required areas are
K6
Level of Evacuation Difficulty
Prompt
> 1.5 ≤ 5.0
s Chapter 32 New
s Chapter 33 Existing
K7
5. SURVEY FOR CERTIFICATION OF: APARTMENT HOUSE LEVEL OF EVACUATION DIFFICULTY (check one)
Slow
> 5.0
s 2000
7.
s Prompt
8.
s
Slow
9.
s
Impractical
Impractical
K5
K8
6. BED COMPOSITION
a. TOTAL NO. OF BEDS IN
THE FACILITY
e. NUMBER OF ICF/MR BEDS
CERTIFIED FOR MEDICAID
s THE FACILITY MEETS, BASED UPON (check all appropriate boxes):
1. s COMPLIANCE WITH ALL PROVISIONS
2. s ACCEPTANCE OF A PLAN OF CORRECTION
B. s THE FACILITY DOES NOT MEET THE STANDARD
e. NUMBER OF ICF/MR BEDS
CERTIFIED FOR MEDICAID
7. A.
4.
s
FSES
5.
s
PERFORMANCE BASED DESIGN
K9
SURVEYOR (Signature)
TITLE
OFFICE
DATE
TITLE
OFFICE
DATE
SURVEYOR ID
K10
FIRE AUTHORITY OFFICIAL (Signature)
According to the Paperwork Reduction Act of 1995, no persons are required to respond to a collection of information unless it displays a valid OMB control number. The valid OMB control number for this information collection is
0938-0242. The time required to complete this information collection is estimated to average 5 minutes per response, including the time to review instructions, search existing data resources, gather the data needed, and complete and
review the information collection. If you have any comments concerning the accuracy of the time estimate(s) or suggestions for improving this form, please write to CMS, Attn: PRA Reports Clearance Officer, 7500 Security Boulevard,
Baltimore, Maryland 21244-1850.
FORM CMS-2786X (06/07) EF 06/2007
Page 1
American LegalNet, Inc.
www.FormsWorkflow.com
INSTRUCTIONS FOR COMPLETING THIS FORM (CMS-2786X)
SUITABILITY OF AN APARTMENT BUILDING TO HOUSE A BOARD AND CARE OCCUPANCY
1. FIRST complete FORM CMS-2786Y (Small Facility Survey Report)
2. NEXT complete THIS form, to rate the suitability of the Apartment Building to House a Board and Care Occupancy.
NOTE: The items on this form refer to the part of the building the Board and Care Occupancy (Apartment).
3. If using NFPA 101A Figure 7.7 — FSES/BC — Rating the Building, complete Part I of this form FIRST.
NOTE: When using this form, you must also complete a CMS 2786Y.
FORM CMS-2786X (06/07) EF 06/2007
Page 2
American LegalNet, Inc.
www.FormsWorkflow.com
ID
PREFIX
SUITABILITY OF AN APARTMENT BUILDING TO HOUSE
A BOARD AND CARE OCCUPANCY
MET
NOT
MET
N/A
REMARKS
APARTMENT
HOUSE
NOTE: You must complete a CMS-2786Y for each Apartment
unit with a Board & Care Occupancy.
BUILDING CONSTRUCTION
K12
Minimum Construction Requirements: (Based on highest story normally
used by residents) PROMPT and SLOW
One and Two Story
u Any construction type of one-hour or greater fire rating or,
u Type IV (2HH) or,
u Fully sheathed or,
u With automatic sprinkler system throughout, in accordance
with Section 9.6 and 9.7.
u Exception: One story any construction type and no more than
30 residents capable of prompt evacuation.
Three to Six Stories
u Type I, II or III construction of one-hour or greater fire rating or,
u Type IV construction with automatic sprinkler system throughout
in accordance with Section 9.6 or 9.7.
u Exception: Three or four story facilities of type V (000), sheathed
and with automatic sprinkler system throughout, in accordance
with Sections 9.6 and 9.7.
More than Six Stories
u Type I or II (222) construction or,
u Type II (111) construction or,
u Type III (211) construction or,
u Type IV (2HH) with automatic sprinkler system throughout in
accordance with Sections 9.6 and 9.7.
Minimum Construction Requirements: (Based on highest story normally
used by residents) PROMPT and SLOW
u Type I or II (222) construction, beyond 75 feet in height with
automatic sprinkler protection throughout in accordance with
Section 9.6 and 9.7.
u Type II (111) construction, limited to three stories with automatic
sprinkler protection throughout in accordance with Sections 9.6
and 9.7
u Type II (000), III (211), IV (2HH), V (111) limited to one story
with automatic sprinkler protection throughout in accordance with
Section 9.6 and 9.7. 32.3.1.3, 33.3.1.3
FORM CMS-2786X (06/07) EF 06/2007
Page 3
American LegalNet, Inc.
www.FormsWorkflow.com
ID
PREFIX
SUITABILITY OF AN APARTMENT BUILDING TO HOUSE
A BOARD AND CARE OCCUPANCY
MET
NOT
MET
N/A
REMARKS
APARTMENT
HOUSE
HAZARDOUS AREAS (Outside B & C Units)
K29
Where buildings are without suppression or detection systems, or have
total automatic detection or partial sprinkler protection every hazardous
area shall be separated by construction of one-hour fire rating. Openings
shall be protected by smoke-actuated automatic or self-closing fire doors,
with a 3/4 hour fire rating or the area is equipped with an automatic
sprinkler system.
Hazardous areas include, but are not limited to:
u Boiler and heater rooms
u Laundries
u Repair shop
u Rooms or spaces used for storage of combustibles or equipment
deemed hazardous by the authority having jurisdiction.
Where buildings have an automatic extinguishment system installed in
accordance with NFPA 13, areas may be smoke-resisting construction.
30.3.2, 31.3.2, 8.4
K211
2000 EXISTING
Where Alcohol Based Hand Rub (ABHR) dispensers are
installed:
t The corridor is at least 6 feet wide
t The maximum individual fluid dispenser capacity shall be
1.2 liters (2 liters in suites of rooms)
t The dispensers shall have a minimum spacing of 4 ft from
each other
t Not more than 10 gallons are used in a single smoke
compartment outside a storage cabinet.
t Dispensers are not installed over or adjacent to an ignition
source.
t If the floor is carpeted, the building is fully sprinklered. 19.3.2.7,
CFR 483.470
FORM CMS-2786X (06/07) EF 06/2007
Page 4
American LegalNet, Inc.
www.FormsWorkflow.com
ID
PREFIX
K211
SUITABILITY OF AN APARTMENT BUILDING TO HOUSE
A BOARD AND CARE OCCUPANCY
MET
NOT
MET
N/A
REMARKS
APARTMENT
HOUSE
2000 NEW
Where Alcohol Based Hand Rub (ABHR) dispensers are
installed:
t The corridor is at least 6 feet wide
t The maximum individual fluid dispenser capacity shall be
1.2 liters (2 liters in suites of rooms)
t The dispensers shall have a minimum spacing of 4 ft from
each other
t Not more than 10 gallons are used in a single smoke
compartment outside a storage cabinet.
t Dispensers are not installed over or adjacent to an ignition
source.
t If the floor is carpeted, the building is fully sprinklered. 18.3.2.7,
CFR 483.470
MANUAL FIRE ALARM
K51
Apartment buildings with more than three stories or more than eleven
units shall have a fire alarm system, not a presignal type, with occupant
notification accomplished automatically and without delay in accordance
with Section 9.6, 30.3.4, 31.3.4.
An annunciator panel shall be provided.
31.3.4.3.2.
K155
Where a required fire alarm system is out of service for more than 4 hours
in a 24-hour period, the authority having jurisdiction shall be notified,
and the building shall be evacuated or an approved fire watch shall be
provided for all parties left unprotected by the shutdown untilt e fire
alarm system has been returned to service. 9.6.1.8
SMOKE DETECTION AND ALARM (Outside B & C)
K109
Every living unit within the apartment building regardless of number of
stories, number of apartments, sprinkler system or other detection system
shall have approved single or multiple station smoke detectors installed,
powered by house electrical service.
u Exception: Where the building is equipped with a total automatic
smoke detection system throughout.
30.3.5, 31.3.4.4
FORM CMS-2786X (06/07) EF 06/2007
Page 5
American LegalNet, Inc.
www.FormsWorkflow.com
ID
PREFIX
SUITABILITY OF AN APARTMENT BUILDING TO HOUSE
A BOARD AND CARE OCCUPANCY
MET
NOT
MET
N/A
REMARKS
APARTMENT
HOUSE
AUTOMATIC SPRINKLER (Outside B & C)
K56
Where buildings are required to be protected throughout by an approved
automatic sprinkler system and where a partial system is required, the
system shall be in accordance with Section 9.7.
30.3.5
K64
Portable fire extinguishers shall be provided in hazardous areas in
accordance with Section 9.7.4.1 unless the building is provided with an
appropriate supervised automatic sprinkler system.
30.3.5.7
K154
Where a required automatic sprinkler system is out of service for more
than 4 hours in a 24-hour period, the authority having jurisdiction shall be
notified, and the building shall be evacuated or an approved fire watch system be provided for all parties left unprotected by the shutdown until the
sprinkler system has been returned to service. 9.7.6.1
A. Date sprinkler system last checked and necessary maintenance
provided. _____________________________________________
B. Show who provided the service. __________________________
C. Note the source of the water supply for the automatic sprinkler
system._______________________________________________
(Provide, in REMARKS, information on coverage for any
non-required or partial automatic sprinkler system.)
SEPARATION OF B. C. UNIT AND ITS EXIT ROUTES
K38
2000 EXISTING
Exit access corridors shall be protected as follows:
u 1. Where buildings do not have an automatic sprinkler or detection
system, corridor walls shall have one-hour fire rating.
u 2. Where buildings have a partial sprinkler or detection system,
corridor walls shall have 3/4 hour fire rating.
u 3. Where buildings have an automatic sprinkler system through,
corridor walls shall have 1/2 hour fire ratings.
31.3.6
FORM CMS-2786X (06/07) EF 06/2007
Page 6
American LegalNet, Inc.
www.FormsWorkflow.com
ID
PREFIX
SUITABILITY OF AN APARTMENT BUILDING TO HOUSE
A BOARD AND CARE OCCUPANCY
MET
NOT
MET
N/A
REMARKS
APARTMENT
HOUSE
2000 New
Exit access corridor walls shall consist of fire barriers in accordance with
8.2.3 that have no less than 1/2 hour fire resistance rating.
Exception: In buildings protected throughout by an approved automatic
sprinkler system in accordance with 29.3.5, no fire resistance rating shall
be required, but the walls and all openings therein shall resist the passage
of smoke.
30.3.6, 32.4.2, 31.3.6
K18
Doors between apartments and corridors shall be self-closing and have a
minimum 20 minute fire rating. 30.3.6.2, 31.3.6.2
EXIT SYSTEM
K32
At least two acceptable exits, remote from each other, are provided for
each floor or fire section. At least half of the required number of units of
exit width shall lead directly to the street.
u Exception No. 1: A living unit with direct exit to street at ground level
or an outside stairway or an enclosed stairway, of one hour fire rating,
serving that unit only, may have a single exit.
u Exception No. 2: Where there are a maximum of four living units per
floor with no more than 20 feet from each unit’s entrance door to an
exit, may have a single exit of a smokeproof tower or outside stair in
accordance with 5.2.3.
u Exception No. 3: Where there is no more than three stories and living
units are separated, vertically and horizontally by 3/4 hour fire rating,
may have a single exit if the stairway is of one hour construction,
serving as access with a maximum of 35 feet from each unit’s
entrance door to exit.
7.3, 30.2.4, 31.2.4, 32.3.2.4
K35
Capacity of exits in number of persons per unit of exit width is in
accordance with 7.3.
30.2.3.1, 31.2.3.1
EXIT ACCESS
K36
Travel distance from the door of a room in a living unit to a corridor door
and a living unit entrance door to the nearest exit are in accordance with
Table A.31.1.
30.2.6.
FORM CMS-2786X (06/07) EF 06/2007
Page 7
American LegalNet, Inc.
www.FormsWorkflow.com
ID
PREFIX
SUITABILITY OF AN APARTMENT BUILDING TO HOUSE
A BOARD AND CARE OCCUPANCY
MET
NOT
MET
N/A
REMARKS
APARTMENT
HOUSE
INTERIOR FINISH
K14
Interior finish on walls, ceilings and floors are in accordance with and
shall apply to the parts of means of egress serving the apartments used as
a residential board and care occupancy.
30.3.3, 31.3.3.
VERTICAL OPENINGS
K20
Stairways, elevator shafts and other vertical openings are in accordance
with 30.3.1, 29.3.1, 31.3.1
SMOKE CONTROL
K24
Exit access corridors shall be provided with smoke barriers in accordance
with Section 8.3. The maximum length of each smoke compartment shall
be 200 feet. Smoke dampers are not required.
u Exception No. 1: Where buildings have an automatic sprinkler
system throughout.
u Exception No. 2: Where exit access is through an atrium 8.2.5.6.
u Exception No. 3: Where exterior exit access provides access to
two exits 7.5.3.
u Exception No. 4: Buildings complying with 31.3.7, Exceptions 1,2,
and 3.
u Exception No. 5: Buildings with exits maximum 50 feet apart.
u Exception No. 6: Where each dwelling unit has direct access to
exterior at grade. 31.3.7, 33.4.3.3.
K44
Horizontal exits required to limit maximum gross area shall be as
specified in 7.2.4.2.
31.2.2.5
SPECIAL FEATURES
K126
Where buildings are greater than six stories with 1 total automatic fire
detection system per N.F.P.A. 72E, but without an automatic sprinkler
system, the interior exit access corridors shall be continuously pressurized
at a minimum of 0.01 inches water, measured at any living unit door.
31.2.11, 7.2.3
FORM CMS-2786X (06/07) EF 06/2007
Page 8
American LegalNet, Inc.
www.FormsWorkflow.com
ID
PREFIX
SUITABILITY OF AN APARTMENT BUILDING TO HOUSE
A BOARD AND CARE OCCUPANCY
MET
NOT
MET
N/A
REMARKS
APARTMENT
HOUSE
BUILDING SERVICES EQUIPMENT
K117
Utilities shall comply with provision of Section 9.1.
32.3.6.1, 33.3.6.1.
K67
Heating, ventilating and air conditioning equipment shall comply with
the provisions of Section 9.2.
32.3.6.2, 33.3.6.2
K118
Elevators, dumbwaiters and vertical conveyors shall comply with the
provisions of Section 9.4.
32.3.6.3, 32.3.6.3.2, 33.3.6.3
K71
Rubbish chutes, incinerators and laundry chutes shall comply with the
provisions of Section 9.5.
32.3.6.4, 33.3.6.4
OPERATING FEATURES
K127
Every required automatic sprinkler system, fire detection and alarm
system, smoke control system, exit lighting, fire door and other item of
equipment required by this code shall be continuously maintained in
proper operating condition.
4.6.12
K72
No furnishings, decorations or other objects are placed to obstruct exits
or visibility of exits. 7.5.2.2
32.7.5
K73
No furnishings or decorations of an explosive or highly flammable
character are used.
18.7.5.4, 19.7.5.4
EMERGENCY PLAN, FIRE DRILLS
K48
There is a written plan for the protection of all persons and for their
evacuation in the event of an emergency. All employees shall be instructed
and reviewed as to their duties and responsibilities under the plan.
32.7.1, 33.7.1
FORM CMS-2786X (06/07) EF 06/2007
Page 9
American LegalNet, Inc.
www.FormsWorkflow.com
ID
PREFIX
K128
SUITABILITY OF AN APARTMENT BUILDING TO HOUSE
A BOARD AND CARE OCCUPANCY
MET
NOT
MET
N/A
REMARKS
APARTMENT
HOUSE
All residents capable of assisting in their evacuation shall be trained in
the proper actions to take in the event of a fire.
32.7.2, 33.7.2
K50
Fire exit drills shall be conducted twelve times per year, quarterly on each
shift. Drills shall involve actual evacuation to a selected assembly point
and provide experience in exiting through all exits. Exits not used in any
fire drill shall not be credited in meeting the requirements of the code.
42 CFR 483.470 Subpart L
K66
Where smoking is permitted, noncombustible safety-type ash trays or
receptacles shall be provided in convenient locations.
32.7.4, 33.7.4
ILLUMINATION AND EMERGENCY POWER
K45
Every public space, hallway, stairway and other means of egress shall
have illumination in accordance with Section 7.8.
30.2.8, 31.2.8
K46
Any apartment building with more than twelve living units or greater
than three stories shall have emergency lighting in accordance with
Section 7.8.
u Exception: Where every living unit has a direct exit to the outside
at grade level.
K47
Signs marking means of egress shall be in accordance with section 7.10
and provided in all apartment buildings requiring more than one exit.
30.2.10, 31.2.10
FORM CMS-2786X (06/07) EF 06/2007
Page 10
American LegalNet, Inc.
www.FormsWorkflow.com
FIRE SAFETY EVALUATION WORKSHEET FOR AN APARTMENT BUILDING
WITH BOARD AND CARE OCCUPANCIES
G3
Building Identification ____________________________________________________________________________________________________
Evaluator ________________________________________________________________Date ___________________________________________
(Complete one worksheet for each apartment house containing one or more apartment units with a board and care occupancy.)
First complete Table 7.7. Continue with Fig. 7.7.1 through 7.7.5. Then return to this page to obtain the Equivalency Conclusions.
TURN TO NEXT PAGE
Part 3E. Equivalency Conclusions
Complete Tables 7.7.2 through 7.7.7 before doing this part.
1. u All of the checks in Table 7.7.7 are in the “YES” column. The level of fire safety is at least equivalent to that prescribed for
apartments.*
2. u One or more of the checks in Table 7.7.7 is in the “NO” column. The level of fire safety is not shown by this system to be equivalent to
that prescribed by the Life Safety Code for apartments.
*The equivalency covered by this worksheet includes the majority of considerations covered by the Life Safety Code. There are a few considerations that are not evaluated by
this method. These must be considered separately. These additional considerations are covered in the “Facility Fire Safety Requirements Worksheet.” One copy of this separate
worksheet is to be completed for each facility.
FACILITY FIRE SAFETY REQUIREMENTS WORKSHEET
CONSIDERATIONS
MET
NOT
MET
N/A
A. Utilities comply with provisions of 9.1
B. Heating, ventilating, and air conditioning equipment
comply with provisions of 9.2.
C. Elevators, dumbwaiters, and vertical conveyors comply
with the provisions of 9.4.
D. Rubbish chutes, incinerators, and laundry chutes comply
with the provisions of 9.5.
E. Complies with the applicable requires of 32.7, 33.7
(Operating Features).
FORM CMS-2786X (06/07) EF 06/2007
Page 11
American LegalNet, Inc.
www.FormsWorkflow.com
Table G-3A
Worksheets for evaluating fire safety for an apartment building with board and care occupancies.
WORKSHEET 7.7.1 COVER SHEET
Fire Safety Evaluation Worksheet for an Apartment Building with Board and Care Occupancies
Building Identification ____________________________________________________________________
Evaluator _________________________________________Date _________________________________
WORKSHEET 7.7.2 SAFETY PARAMETER VALUES — APARTMENT BUILDING
Safety Parameters
Parameter Values
Combustible
1. Construction
Building Height
1 Story
2 Stories
3-4 Stories
5-6 Stories
Over 6 Stories
2. Hazardous Areas
(outside board &
care home units)
3. Manual Fire Alarm
4. Smoke Detection and
Alarm (outside board
& care home units)
5. Automatic Sprinklers
(outside board & care
home units)
6. Separation of
Board & Care Home
Unit and Its Exit Route
from Other Spaces
7. Exit System (serving
board & care home
units)
8. Exit Access (serving
board & care home
units)
9. Interior Finish (egress
routes serving board &
care home units)
FORM CMS-2786X (06/07) EF 06/2007
Noncombustible
Type V
(000)
Type V
(111)
Type III
(200)
Type III
(211)
Type IV
(2HH)
Type II
(000)
Type II
(111)
-2( )a
-6( )a
-8( )a
-8
-10
0
0
-2(0)k
-2(0)k
-4
Double
Deficiency
-4(-7)b.g
None or
Incomplete
0(2)i
-2( )a
-6( )a
-8( )a
-8( )a
-10
0
0
0
0
-2(0)k
0
0
-2(0)k
-2(0)k
-4(0)k
0
-5( )a
-6( )a
-6( )a
-8
2
2
2
2
0
None or No
Deficiency
0
Single
Deficiency
0(-4)g
Type II (222)
& Type I
2
2
2
2
2
Manual Alarm
w/o F.D. Notification
w/F.D. Notification
2
3
Interconnected System
Single Station
Corrs. &
Corrs., Common
None or
Living Units Only
Common
Spaces, & Living
Total
Incomplete
Single Level
Every Level
Spaces
Units
Building
-4(0)j
0
-2(0)e
-3(0)3
4
6
None or
Corrs., Public
Living Units
Corrs., Hab., &
Total
Incomplete
Space
Only
Public Spaces
Building
4(0)c
6
8
0
2(0)c
Walls 30 min to 1 hr
Doors20
Doors20
Doors 20
None or
min w/o
min w/o
min
min
min
min
Incomplete
Closer
Closer
w/Closer
w/Closer
w/Closer
w/Closer
1(-2)b
2(-2)b
1(-2)b
4(-2)b
-6
-2
0(-2)b
50 ft and
>50 ft or corridor
>150 ft
>100 ft
>50 ft
to 200 ft
to 75 to 25 to
0
Egress
Provided (S2)
minus
Required
Egress (Sb)
>
0
Refuge
Provided (S3)
minus
Required
Refuge (Sc)
>
0
General
Fire Safety (S4)
minus
Required General
Fire Safety (Sd)
>
0
NO
–
=
Sb
S2
–
=
Sc
S3
–
=
Sd
S4
–
=
WORKSHEET 7.7.6 FACILITY FIRE SAFETY REQUIREMENTS WORKSHEET
CONSIDERATIONS
A.
NOT
MET
N/A
Utilities comply with the provisions of 32.3.6.1 and 33.3.6.1.
B.
MET
Heating, ventilating, and air conditioning equipment comply with the provisions of 32.3.6.2
and 33.3.6.2, except for enclosure of vertical openings, which have been considered in Safety
Parameter 10 of Worksheet 7.7.2.
Elevators, dumbwaiters, and vertical conveyors comply with the provisions of 32.3.6.3
and 33.3.6.3.
C.
D.
Rubbish chutes, incinerators, and laundry chutes comply with the provisions of 32.3.6.4
and 33.3.6.5.
E.
Complies with the applicable requirements of Sections 32.7 and 33.7.
All references are to NFPA 101, Life Safety Code
WORKSHEET 7.7.7 CONCLUSIONS
1. u All of the checks in Worksheet 7.7.5 are in the “YES” column. The level of fire safety is at least equivalent to that
prescribed by NFPA 101, Life Safety Code, for apartments to house a board and care occupancy.*
2. u One or more of the checks in Worksheet 7.7.5 are in the “NO” column. The level of fire safety is not shown by this
system to be equivalent to that prescribed by NFPA 101 for apartments to house board and care occupancy.
*The equivalency covered by this worksheet includes the majority of considerations covered by NFPA 101, Life Safety Code.
There are some considerations that are not evaluated by this method. These must be considered separately. These additional
considerations are covered in Worksheet 7.7.6, “Facility Fire Safety Requirements Worksheet.” One copy of this worksheet is
to be completed for each facility.
FORM CMS-2786X (06/07) EF 06/2007
Page 15
American LegalNet, Inc.
www.FormsWorkflow.com
FIRE SAFETY SURVEY REPORT
CRUCIAL DATA EXTRACT
(TO BE USED WITH CMS-2786 FORMS)
PROVIDER NUMBER
FACILITY NAME
SURVEY DATE
K1
K6
* K4
K3
DATE OF PLAN
APPROVAL
MULTIPLE CONSTRUCTION
TOTAL NUMBER OF BUILDINGS ____________
NUMBER OF THIS BUILDING
LSC FORM INDICATOR
____________
12
13
14
15
SMALL
(16 BEDS OR LESS)
K8:
ASC Form
2000 EXISTING
2000 NEW
1 PROMPT
2 SLOW
3 IMPRACTICAL
LARGE
K8:
ICF/MR Form
2786V, W, X
2000 EXISTING
2786V, W, X
2000 NEW
16
17
SELECT NUMBER OF FORM USED FROM ABOVE
*K9:
7 PROMPT
8 SLOW
9 IMPRACTICAL
ENTER E – SCORE HERE
(Check if K29 or K56 are marked as not applicable
in the 2786 M, R, T, U, V, W, X and Y.)
K29:
4 PROMPT
5 SLOW
6 IMPRACTICAL
APARTMENT HOUSE
K8:
* K7
BUILDING
WING
FLOOR
APARTMENT UNIT
COMPLETE IF ICF/MR IS SURVEYED UNDER CHAPTER 21
Health Care Form
2786R
2000 EXISTING
2786R
2000 NEW
2786U
2786U
A
B
C
D
K5:
K56:
e.g. 2.5
FACILITY MEETS LSC BASED ON (Check all that apply)
A1.
(COMP. WITH
ALL PROVISIONS)
A2.
A3.
(ACCEPTABLE POC)
FACILITY DOES NOT MEET LSC
(WAIVERS)
A5.
(FSES)
(PERFORMANCE
BASED DESIGN)
K0180
A.
B.
A4.
FULLY SPRINKLERED
B.
PARTIALLY SPRINKLERED
(All required areas are sprinklered) (Not all required areas are sprinklered)
C.
NONE
(No sprinkler system)
* MANDATORY